High Profile Power Analyser - Load Manager, Data Logger, Dynamic Communication
Power/eNavigator, a sophisticated Power Analyzer that enables user to navigate the full scope of an electrical network and empowers to manage power efficiently.
The instrument offers versatile and unmatched features and functions to monitor, profile,record events, control,data logging, protect and even check the quality of an electrical system.
Power/eNavigator is built to be a single point solution to meet your energy maangement needs.
Applications
Automatic connection or disconnection of Gensets connected to common bus.
Protection of equipment from Under/Over Voltage or Current or Frequency
Protection of 3 phase equipment from Single phase prevention, Overload etc.
Programmable Auto Scrolling time 1 sec. to 10 sec. (Default 5 sec.)
Pulse output (POP) on time 50-500ms user programmable
Dynamic Communication - user selectable register map
Programmable - Energy display counter based on resolution base.
Energy resetting @ 999999kWH * Multiplication factor
Reverse lock option user programmable for positive eneergy accumulation
Front LED pulse 5000 imp/kWH
% of unbalance V & A for all three phases
THD for Voltage and Current (upto 31st)
Ampere hour (Ah) and PF average parameters
Upgradable to higher versions
Accuracy : Class 1 (Default) IEC 61036, IS 13779, CBIP 88, Class 0.5 (Option)
Sensing/Measurement : True RMS, 1 Sec update time, 4 Quadrant Power and Energy (RD Option)
Input voltage : 4 Voltage inputs (VR, VY, VB, VN), Programmable 110 or 415V LL Nominal, (Range 80 to 550V LL), Primary Programmable up to 999 kV, Burden: 0.2VA Max. per phase.
Input current : Current inputs (AR, AY, AB) 50mA - 6A, (Field configurable 1A or 5A), Primary Programmable up to 99 kA, Overload: 10A max continuous, 50A max for 3 sec, Burden: 0.2VA Max. per phase.
Aux-Supply : (Control Power)80 - 300V AC/DC (Default), 48V DC Option, Burden : 4VA Max
Display Type : eNavigator : 10mm height bright red LED display, Power Navigator : 6 mm height bright LCD gaphical display
Display Resolution : 4 digits for instantaneous, Integrated : EN - 6 digits,PN - 7 digits
CT PT Ratio Max : 2000 MVA Programmable
Communication : RS485 serial channel connection, Industry standard Modbus RTU protocol (RS232 optional), Baud rate: 2400 bps to 19200 bps. (Preferred 9600 bps), Isolation : 2000 volts AC isolation for 1 minute between communication and other circuits.